ZIEHL industrie – elektronik GmbH + Co KG Daimlerstraße 13, D – 74523 Schwäbisch Hall + 49 791 504-0, [email protected], www.ziehl.de Temper
TR440 12310-0702-04 Seite 10 / 24 www.ziehl.de 8.5 Short operating diagram [Program 1] Configuration mode Menu mode Display mode Stop bit: f
TR440 12310-0702-04 Seite 11 / 24 www.ziehl.de 8.6 Short operating diagram [Program 2] Menu mode Configuration mode Display mode Stop bit:
TR440 12310-0702-04 Seite 12 / 24 www.ziehl.de 8.7 Short operating diagram [Program 3] Menu mode Configuration mode Display mode Stop bit: f
TR440 12310-0702-04 Seite 13 / 24 www.ziehl.de 8.8 Short operating diagram [Program 4] Menu mode Configuration mode Display mode Stop bit: f
TR440 12310-0702-04 Seite 14 / 24 www.ziehl.de 8.9 Overview of commissioning Must Can Overview X 8.10 Selection of program number X 8.11
TR440 12310-0702-04 Seite 15 / 24 www.ziehl.de 8.13 Configure the alarms The following parameters are significant: Alarm value 8FAN.8 8ALR.8
TR440 12310-0702-04 Seite 16 / 24 www.ziehl.de Set the desired value with the Up and Down keys Press the Set key Display 8rel .8 / 8 r.8
TR440 12310-0702-04 Seite 17 / 24 www.ziehl.de 8.15 Configure the Modbus RS 485 interface (option) The following parameters are significant:
TR440 12310-0702-04 Seite 18 / 24 www.ziehl.de 8.17 Code block Here, the set parameters can be protected by activating a code block. The devi
TR440 12310-0702-04 Seite 19 / 24 www.ziehl.de 8.19 Possible indications in display In display mode (normal state) 8alr8 / 8trp8 / 8Cor8 Al
TR440 12310-0702-04 Seite 2 / 24 www.ziehl.de Table of contents 1 Use and brief description ...
TR440 12310-0702-04 Seite 20 / 24 www.ziehl.de Simulation, menu mode/configuration mode 8Si .8 Simulation 8S1-3.8 / 8S 4.8 Sensor to be simula
TR440 12310-0702-04 Seite 21 / 24 www.ziehl.de Alarm Relay K4 Alarm name 8Err8 8Err8 8COR8 8Err8 - - - Limit - - - - - - 81708 - - - 8H 8 (
TR440 12310-0702-04 Seite 22 / 24 www.ziehl.de The device cannot be programmed (configured) Cause Code block Remedy The code block provides pr
TR440 12310-0702-04 Seite 23 / 24 www.ziehl.de 12 Technical data Control voltage Us AC/DC 24 – 240 V 0/50/60 Hz <2 W < 4 VA Limits
TR440 12310-0702-04 Seite 24 / 24 www.ziehl.de Housing Panel monitoring housing SE 2 Dimensions (W x H x D) 96 x 96 x 80 mm Line connection si
TR440 12310-0702-04 Seite 3 / 24 www.ziehl.de 1 Use and brief description Temperature relay to protect transformers against excess temperat
TR440 12310-0702-04 Seite 4 / 24 www.ziehl.de Program 1: Program 2: 3 sensors in the windings: 3 sensors in the windings and 1 sensor in the t
TR440 12310-0702-04 Seite 5 / 24 www.ziehl.de 4 Display and controls 1 Digital display (3 digits) Display of sensor value Display
TR440 12310-0702-04 Seite 6 / 24 www.ziehl.de 5 Important information WARNING Hazardous electrical voltage! Can lead to electric sho
TR440 12310-0702-04 Seite 7 / 24 www.ziehl.de 6 Programs 4 programs (Pr) can be selected in the factory version. Starting from these program
TR440 12310-0702-04 Seite 8 / 24 www.ziehl.de 8 Start-up operation (commissioning) 8.1 General instructions on operating On the decimal p
TR440 12310-0702-04 Seite 9 / 24 www.ziehl.de 8.3 Menu mode Decimal point on Select the menu items for viewing the parameters Function keys